4.2.5.1.2. Range
A Fixed Range Constant that refers to the three user-selectable ranges of
proportional current; 0 to 20mA, 4 to 20mA and –20 to +20mA.
From the Analog Output SETUP pages previously described use
to navigate to
Range. Depress
to toggle through 0 to 20mA, 4 to
20mA and –20 to +20mA. When complete, navigate to the
next constant using
or save changes as described in
section 4.1.2.
4.2.5.1.3. Min / Max Value
Min / Max Value are Variable Range Constants used to define the
endpoints in the operating window of the output current. The Min Value
e minimum current.
aximum
of
ployed, values of –2 kHz to 2 kHz
vely and 0kHz will produce 0mA.
defines the Input source value that will produce th
Max Value defines the Input source value that will produce the m
current. For example, if the selected range is 0 to 20 mA , a Min Value
1 kHz will produce 0 mA and a Max Value of 2 kHz will produce 20
mA. Since the output is proportional to the input and response is linear, it
is easy to calculate expected values within the defined value limits.
Therefore an input value of 1.5 kHz is at 50% scale and will yield 10mA.
In the event direction detection is em
will yield –20 and +20 mA respecti